Magnetic Properties Simulation of Electrical Steel Sheet Based on Recurrent Neural Network
Harmonics change both the shape and area of the hysteresis loop in electrical steel. In the harmonic tests reported in the paper, the recurrent model predicted total loss with an error below 3%.
Harmonic and DC Bias Hysteresis Characteristics Simulation Based on an Improved Preisach Model
DC bias makes the hysteresis loop of grain-oriented steel asymmetric. The team used measured limiting loops to generate first-order reversal curves and construct Everett functions for different bias fields. Measurements under harmonic excitation and DC bias were used to test the model.
Measurement and Simulation of Magnetic Properties of Nanocrystalline Alloys under High-Frequency Pulse Excitation
With the pulse voltage held constant, increasing the repetition rate or reducing the duty cycle narrowed the measured minor hysteresis loops. At 1 kHz the field–circuit simulation showed the core reaching saturation after five pulses at 5% duty and nine pulses at 1% duty.
Simplified Calculation Model for Contact Resistance Based on Fractal Rough Surfaces Method
The apparent contact area of two conductors hides the small patches that actually carry current. A statistical model links those patches and a surface film to contact resistance. Among the surfaces studied at a given load, a fractal dimension of 1.5 gave the lowest resistance.
Magnetic properties deterioration of non-oriented steel due to laser cutting
How far does the effect of a laser cut extend into a motor lamination? Local hysteresis measurements on 35WW250 electrical steel detected magnetic degradation as far as 18 mm from the cut edge. Magneto-optical images showed how the domain pattern changed across the same region.
Yue Shuaichao PHD Defence
Hebei university of Technology PHD Defence
Sun Changxing PHD Defence
Hebei university of Technology PHD Defence
Punching effects on local magnetic properties near the edge of nonoriented electrical steels
A miniature B–H sensor mapped magnetic damage inward from a punched edge. In sheets punched at 80 and 250 MPa, the affected regions extended about 6 and 12 mm from the edge, respectively. Local loss measurements showed how much of the increase came from hysteresis and excess loss.
Modeling and Validation of Stray-Field Loss in Laminated Magnetic Shield of Transformer under Harmonics and DC Bias
A modified TEAM P21 benchmark provided a common test for measured and calculated losses in a laminated transformer shield. For cases III and IV, using magnetic properties measured under the actual nonsinusoidal excitation reduced the loss errors from 6.17% and 7.00% to 2.36% and 2.93%, respectively.
Thermal Network Model of High-Power Dry-Type Transformer Coupled With Electromagnetic Loss
A thermal network divided the windings of a 2,500 kVA dry-type transformer into 11 regions and accounted for differences in electromagnetic loss and cooling along the ducts. The temperature-rise study located the hot spot at the top of the outermost high-voltage winding, at 151.8 °C.